Problem

In order to increase production rate, a reactor setpoint was increased from 160 psig to 19...

In order to increase production rate, a reactor setpoint was increased from 160 psig to 190 psig. The reactor pressure transmitter was recalibrated from 0–200 psig to 0–300 psig. What is the percent span for the old and new setpoints?

a. 50%

b. 63%

c. 80%

d. 90%

Remember: In an operating unit, when a transmitter is recalibrated, the scale must be changed on the controller as well as the controller retimed.

Step-by-Step Solution

Request Professional Solution

Request Solution!

We need at least 10 more requests to produce the solution.

0 / 10 have requested this problem solution

The more requests, the faster the answer.

Request! (Login Required)


All students who have requested the solution will be notified once they are available.
Add your Solution
Textbook Solutions and Answers Search
Solutions For Problems in Chapter 9