A professional center is supplied by a balanced three- phase source. The center has four balanced three-phase loads as follows:
Load 1:150 kVA at 0.8 pf leading
Load 2:100 kW at unity pf
Load 3: 200 kVA at 0.6 pf lagging
Load 4: 80 kW and 95 kVAR(inductive)
If the line impedance is 0.02 + j0.05 Ω per phase and the line voltage at the loads is 480 V, find the magnitude of the line voltage at the source.